Regarding the original question, of whether or not a 50 Amp circuit, wired in 6 AWG is permissible to serve this 37.5 A load; you should have no problems, so long as nothing else is on this circuit. NEC 210.23 Permissible loads states: "An individual branch circuit shall be permitted to supply...