Default Outlet Connect Questions

So this is pretty straight forward, but a little bit of a precurser: I'm looking to install a 2000watt heating element into my boil kettle. I checked the circuit in my kitchen, its 20amps, the GFCI outlet is a 20amp outlet, the wiring is all 12/3 wiring, and the only thing on this circuit is my garbage disposal (which won't be on when I'm brewing).

Everything looks good, but as I started looking for a cable to use for running this connection, I noticed there is a difference between L5/15 connectors and L5/20 connectors. I'm under the impression that L5/15 connectors are for 15 amp loads, and that L5/20 are for 20 amp loads.

My problem is all my outlets only accept L5/15 connectors. Can an L5/15 connector support a 20amp load? I dont want to overload the connector, but I have found an L5/15 12/3 extension cord I was planning to use for it. Am I going to have issues with that connector? Or is the difference just to prevent people from plugging it into a 15amp circuit? Thanks in advance!

__________________

Reason: formatting
hustlebird is offline
 
Reply With Quote Quick reply to this message
Old 01-30-2013, 03:04 PM   #2
Bensiff
Mind Your Business
HBT_SUPPORTER.png
Feedback Score: 0 reviews
 
Bensiff's Avatar
Recipes 
 
Join Date: Mar 2008
Location: , Washington, the state
Posts: 4,494
Liked 305 Times on 245 Posts
Likes Given: 53

Default

You are correct, an L5-15 is rated for 15 amp 125v service. You might consider tying in a box with the L5-20 connector. Personally, I have been shocked and electricity owns my complete respect so I don't ever consider going beyond somethings ratings.

How big a kettle are you talking about? 2000w isn't a lot of energy.

__________________
Bensiff is offline
 
Reply With Quote Quick reply to this message
Old 01-31-2013, 01:35 AM   #3
hustlebird
HBT_LIFETIMESUPPORTER.png
Feedback Score: 0 reviews
Recipes 
 
Join Date: Oct 2012
Location: , Alexandria, VA
Posts: 79
Liked 2 Times on 2 Posts
Likes Given: 2

Default

Dang, I figured as much. Guess ill just replace my gfci with a gfci outlet that can accept l5-15 and l5-20. I just thought that the connectors may be able to handle more, because the l5-20 just seems like a sideways version of the l5-15.

Either way, for an extra 20 bucks for the gfci outlet isn't a big deal.

I have a ten gallon kettle, brew five gallon batches, and this is to supplement the range I cook on, sick of dealing with a bucket heater (1350 watts) and its a little weaker then I'd like still.

__________________
hustlebird is offline
 
Reply With Quote Quick reply to this message
Reply



Quick Reply
Message:
Options
Thread Tools


Similar Threads
Thread Thread Starter Forum Replies Last Post
chugger pump with a switched outlet and constant outlet Rivenin DIY Projects 1 05-19-2012 05:06 AM
Getting 240VAC outlet in kitchen .. oven outlet? jdonagher Electric Brewing 12 01-30-2012 01:57 AM
How to connect 2 shafts? imperialipa DIY Projects 13 10-17-2011 05:47 PM
Sparge arm help. Connect to lid? mr_tripp All Grain & Partial Mash Brewing 4 01-07-2010 10:59 PM
How do you connect to newsgroups? alt. TxBrew General Chit Chat 3 03-13-2005 08:56 PM