Using 2 pumps at the same time
|
|
I've got a fairly basic question. I'm upgrading my brew system, and I now have 2 March 815 pumps. I am wondering about running both pumps at the same time. Will they need to be plugged into separate circuits? Or can they run at the same time on the same circuit? I brew out of my garage, and there are only 2 outlets in there, both on the same circuit.
|
|
|
03-14-2012, 12:47 AM
|
#2
|
|
Feedback Score: 0 reviews
Join Date: Feb 2011
Location: Joliet, IL
Posts: 1,115
Liked 147 Times on 87 Posts Likes Given: 3
|
Quote:
Originally Posted by willeck2
I've got a fairly basic question. I'm upgrading my brew system, and I now have 2 March 815 pumps. I am wondering about running both pumps at the same time. Will they need to be plugged into separate circuits? Or can they run at the same time on the same circuit? I brew out of my garage, and there are only 2 outlets in there, both on the same circuit.
|
I'm wondering about two pumps running at the same time as well. As in, "why would you ever need two pumps running at the same time?"
The only thing I can think of is if you're draining the MLT into a BK with pump #1 while pump #2 is draining the HLT into the MLT while you're fly sparging.
|
|
|
03-14-2012, 12:51 AM
|
#3
|
|
Feedback Score: 0 reviews
Join Date: Feb 2012
Location: Manassas, VA
Posts: 438
Liked 6 Times on 6 Posts Likes Given: 11
|
^^^ Yup... I use two pumps for that as well. on a single-tier system you really need two.
Also you could be using one to recirculate your Mash through a RIMS while using one to recirculate your sparge water through another RIMS in the HLT.
|
|
|
03-14-2012, 01:26 AM
|
#4
|
|
Feedback Score: 0 reviews
Join Date: Nov 2008
Posts: 2,073
Liked 16 Times on 15 Posts
|
You should be able to run 2 on a 15 amp circuit with no problem.
(Unless you have a lot of other stuff on the same circuit)
Ed
|
|
|
03-14-2012, 01:26 AM
|
#5
|
|
Feedback Score: 0 reviews
Join Date: May 2011
Location: plattsburgh, New York
Posts: 11
|
Fly sparring is exactly why I'm asking. That is the only time I think I would be running both pumps, also maybe when I'm running cleaner through the system after a brew. So can anyone tell me if I'll need to run an extension cord into my house to pick up on another circuit?
|
|
|
03-14-2012, 01:30 AM
|
#6
|
|
Feedback Score: 0 reviews
Join Date: Feb 2012
Location: Manassas, VA
Posts: 438
Liked 6 Times on 6 Posts Likes Given: 11
|
according to the manual March 815 pumps (110V variety) draw 1.4 Amps. Sounds totally doable.
|
|
|
03-14-2012, 01:31 AM
|
#7
|
|
Feedback Score: 0 reviews
Join Date: May 2011
Location: plattsburgh, New York
Posts: 11
|
Thanks Ed, I didn't think that two pumps would overload a circuit, but I'm no electrical genius. I thought that I'd previously read something about 2 pumps being too much for one circuit, but I looked all day and couldn't find it, so I figured I'd ask others who have already done it.
|
|
|
03-14-2012, 01:31 AM
|
#8
|
|
Feedback Score: 0 reviews
Join Date: Feb 2012
Location: Manassas, VA
Posts: 438
Liked 6 Times on 6 Posts Likes Given: 11
|
|
|
|
03-14-2012, 01:35 AM
|
#9
|
|
Feedback Score: 0 reviews
Join Date: May 2011
Location: plattsburgh, New York
Posts: 11
|
Thanks Scott, I was hoping to be able to be able to wire both pumps to 1 outlet attached to my brew stand, and then just have a plug running from the outlet to plug into one of my wall plugs.
|
|
|
03-14-2012, 02:28 AM
|
#10
|
|
Feedback Score: 0 reviews
Join Date: Dec 2011
Posts: 294
Liked 13 Times on 11 Posts Likes Given: 9
|
+1
I run two pumps off of one circuit ALL the time.
|
|
|